Emotron AB 01-2550-01r3 Parameter list 21
9.1 Terminals
1)
Note! Terminals 1 and 2 (S1, S2) carry line voltage.
2)
N must be connected to terminal 11 and 13 (single phase).
Table 5 Terminals and labels
Terminal Label Function
1S1
Current transformer input for CTM 010, CTM 025 or
CTM 050, blue wire
1
2 S2 Current transformer input, brown wire
1)
3(not used)
4(not used)
5RES
Reset input. Latched or unlatched alarm is selected via
this input. Connect to + at DC.
6C
Alarm relay common and also reset common. Connect to
“-” at DC.
7 NC Alarm relay normally closed
8 NO Alarm relay normally open
9 L1 Motor voltage phase L1
10 (not used)
11 L2 Motor voltage phase L2 (N for single phase motors)
2)
12 (not used)
13 L3 Motor voltage phase L3 (N for single phase motors)
2)