Crompton-controls M10 Bedienungsanleitung Seite 20

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 34
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 19
18 Programming Emotron AB 01-2550-01r3
More hints
If the alarm level is difficult to set - simply perform an Auto Set when the
motor is stopped. Then start the machine, run at normal load and perform
an Auto Set again.
If a wrong value is unintentionally set - simply set a new value. If the value is
not confirmed by pressing PAR, the new value is not accepted (time out
after 30 seconds).
Table 2 Parameters and values.
Parameter Value
Factory
setting
Note
RATED POWER 0 1 2 4 8 16 32 64 64 See table 3
RELAY INVERTED 0 (no) 1 (yes) 0 0 = Relay activated at alarm
ALARM
CURRENT = 0
0 (no) 1 (yes) 0 Alarm at no motor current
MAX OR MIN 0 (MIN) 1 (MAX) 1
0 = under load
1 = overload alarm
RESPONSE
DELAY
0 1 2 4 8 16 32 64 2
Response delay in seconds
(0=50 ms)
START DELAY 0 1 2 4 8 16 32 64 2 Start delay in seconds
MARGIN (% of
rated power)
0 1 2 4 8 16 32 64 8
Load change for alarm
sensitivity, Fig. 7
AUTO SET
Auto Set load level is
automatically set if
VAL key is pressed for
3 seconds.
VAL key must be pressed
when LED parameter AUTO
SET is light. LED bar is
switched off when Auto Set
level is set.
Seitenansicht 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 33 34

Kommentare zu diesen Handbüchern

Keine Kommentare